设备安装参考数据T00机柜

发布于 2022-10-15 05:14:35 字数 2511 浏览 19 评论 0

设备安装参考数据T00机柜

RS/6000, P系列
T00机柜的机房安装参考数据.
Model T00 Rack
Dimensions
Height 1804 mm 71.0 in.
Capacity 36 EIA Units
With PDP - DC only 1926 mm 75.8 in.
Width without side
panels
623 mm 24.5 in.
With side panels 644 mm 25.4 in.
Depth with rear door
only
1042 mm 41.0 in.
Depth with rear door
and RS/6000 style
front door
1098 mm 43.3 in.
pSeries (sculptured)
style front door
1147 mm 45.2 in.
Weight
Base Rack 244 kg 535 lbs
Full Rack1 816 kg 1795 lbs
See 乬T00 and T42 Rack Weight Distribution and Floor Loading乭 on page 34.
Electrical2 (sum specified values for
drawers or enclosures in rack)
DC Rack
Power source loading
maximum in kVA3
8.4
Voltage range (V dc) -40 to -60
AC Rack
Power source loading
maximum in kVA (per
PDB).
4.8
Voltage range (V ac) 200 to 240
Frequency (hertz) 50 or 60
Temperature
Requirements
(see specifications for drawers or enclosures)
Humidity
Requirements
(see specifications for drawers or enclosures)
Noise Emissions (see specifications for drawers or enclosures)
Clearances Front Back Left Right
Install/Air Flow Rack airflow requirements are a function of the number and type of drawers installed (see
note 5). Please refer to the individual drawer specifications.
Service 915mm(36 in) 915mm(36 in) 915mm(36 in) 915mm(36 in)

1. Configuration dependent, base rack weight plus the weight of the drawers mounted in the rack. The rack can
support up to a maximum weight of 35 lbs/EIA (Unit).

2. The total rack power should be derived from the sum of the power used by the drawers in the rack.

3. The Power Distribution Panel (PDP) on the DC powered rack can hold up to eighteen (nine per power source) 48
volt 20 to 50 amp circuit breakers (configuration dependent). Each power source supports up to 8.4 kVA.

4. Each AC Power Distribution Bus (PDB) can supply 4.8 kVA. A rack can have up to four PDB’s as required by the
drawers mounted in the rack.

5. All rack installations require careful site and facilities planning designed to both address the cumulative drawer
heat output and provide the airflow volumes rates necessary to comply with drawer temperature requirements.

如果你对这篇内容有疑问,欢迎到本站社区发帖提问 参与讨论,获取更多帮助,或者扫码二维码加入 Web 技术交流群。

扫码二维码加入Web技术交流群

发布评论

需要 登录 才能够评论, 你可以免费 注册 一个本站的账号。
列表为空,暂无数据
我们使用 Cookies 和其他技术来定制您的体验包括您的登录状态等。通过阅读我们的 隐私政策 了解更多相关信息。 单击 接受 或继续使用网站,即表示您同意使用 Cookies 和您的相关数据。
原文