设备安装参考数据44P-270

发布于 2022-10-15 05:14:29 字数 1936 浏览 15 评论 0

设备安装参考数据44P-270

RS/6000, p系列
44p-270的机房安装参考数据
7044 44P Series Model 270
Dimensions
Height 610 mm 24.0 in.
Width 222 mm 8.7 in.
Width with Pedestal 340 mm 13.4 in.
Depth 713 mm 28.1 in.
Weight
Minimum configuration 37 kg 80 lbs.
Maximum configuration 45 kg 97 lbs.
Electrical
Power source loading 0.47
(maximum in kVA)
Voltage range (V ac) 100 to 127 or 200 to 240 (autoranging)
Frequency (hertz) 50 to 60
Thermal output (typical) 1012 Btu/hr
Thermal output (maximum) 1518 Btu/hr
Power requirements (typical) 297 watts
Power requirements (maximum) 445 watts
Power factor 0.92 to 0.99
Inrush current3 30 amps at 120 V ac, 32 amps at 240 V ac
Maximum altitude 2135 m (7000 ft.)
Temperature Requirements Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity Requirements Operating Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 23°C (73°F) 27°C (80°F)
Noise Emissions1 Operating Idle
LWAd 5.5 bels 5.4 bels
LpAm N/A N/A
<LpA>m 37 dBA 36 dBA
Impulsive or prominent discrete tones No No
Clearances Front Back Left Right
Install/Air Flow2 76mm(3 in) 152mm(6 in) 51mm(2 in) 51mm(2 in)
Service Install so that it can be moved to an area providing 457mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Footprint2 Width
324mm(12.7 in)
Depth
940mm(36.6 in)

1. See “Noise Emission Notes” on page 199 for definitions of noise emissions positions.

2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.

3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.

如果你对这篇内容有疑问,欢迎到本站社区发帖提问 参与讨论,获取更多帮助,或者扫码二维码加入 Web 技术交流群。

扫码二维码加入Web技术交流群

发布评论

需要 登录 才能够评论, 你可以免费 注册 一个本站的账号。
列表为空,暂无数据
我们使用 Cookies 和其他技术来定制您的体验包括您的登录状态等。通过阅读我们的 隐私政策 了解更多相关信息。 单击 接受 或继续使用网站,即表示您同意使用 Cookies 和您的相关数据。
原文